1296 square inches with the width and or height of exposed glass not to exceed 54.
Maximum glass in b rated door.
Ul its wh allow one 1 light with 100 square inches 06 square meters maximum of glass is permitted on 3 hour.
Maximum width of 12 305 mm or height of 33 838 mm.
If the door serves as a horizontal exit door in a fire wall it is fur ther restricted to 100 sq.
Limited to one 1 light per door leaf with a maximum of 100 square inches of exposed glass.
Inches with no dimension exceed ing 10 inches.
3 hour doors are not permitted to have fire protection rated glass.
5268 square inches with the width and or height of exposed glass not to exceed 109 3 4.
Wire glass not approved for use in 3 hour fire doors.
Wire glass 100 square inches is max exposed glass when wire glass is used.
Glass lights are available in fire rated t series doors.
This applies to all hourly ratings a.
L b t series doors if firelite or other 3 hour listed glazing material is used.
For listed 1 4 wire glass the maximum sizes are.
All glass being used in a fire rated opening must be an approved listed glazing material.
Fire rated doors and frames are covered including a chart of the minute hour ratings maximum glass size and other requirements.
Fire resistance rated glazing in excess of 100 square inches 0 065m 2 shall be permitted in fire door assemblies when tested as components of the door assemblies and not as glass lights and shall have the maximum end temperature rise of 450 degrees f 250 degrees c in accordance with 716 5 5.
Note many code are outlawing the use of wire glass due to the hazards of injury from glass breakage.
Ul labels are also discussed.
A recently finalized revision to the ibc model building code limits the size of fire protective glazing such as safety wired glass and safety ceramic used within vision panels for 60 or 90 minute temperature rise doors to no more than 100 square inches whether or not sprinklers are present.
Some local building codes do not recognize the use of glass lights in 3 hour fire doors.
60 and 90 minute doors to 100 sq.
20 45 minute doors still require fire protection rated glass up to the maximum size.
If the door serves as a horizontal exit door in a fire wall it is further restricted to 100 sq.